In short
Special suppression covers every fixed extinguishing system that is not plain water: foam for flammable-liquid pool fires, carbon dioxide and inert gases that act by oxygen dilution, halocarbon clean agents that break the combustion chain, plus water mist, dry chemical powder, wet chemical and condensed aerosol. These systems protect risks where water would spread the fire (oil tanks), damage the asset (server rooms, switchgear, museums) or fail to reach it (turbine enclosures, cable tunnels, kitchen ducts). The subject is examined in Fire Protection Engineering papers through agent selection, flooding-quantity calculation and foam application rates, and is tested in interviews at refineries and terminals (IOCL, BPCL, HPCL, ONGC, Reliance, Adani), data-centre and OEM firms (Siemens, Honeywell, Johnson Controls, Minimax, Ceasefire, HD Fire Protect, Newage Industries), and in third-party inspection and insurance-survey roles. The governing documents in India are NBC 2016 Part 4, the relevant Indian Standards, OISD standards for the hydrocarbon sector, and NFPA/ISO codes adopted by insurers and consultants.
Explained
Mechanisms, fire classes and agent selection
- Four suppression mechanisms: cooling (water, mist), smothering / oxygen dilution (foam blanket, CO₂, inert gases), chemical chain-breaking by scavenging H· and OH· radicals (halons, halocarbons, dry and wet chemical, potassium aerosol) and fuel separation (foam blanket sealing vapours).
- Fire classes used in Indian practice (IS 15683 / IS 2190 for portables): A carbonaceous solids, B flammable liquids, C flammable gases, D combustible metals, F (also called K) cooking oils and fats; energised electrical equipment is a condition, not a class, and demands a non-conducting agent.
- Selection logic: fuel type and geometry → occupancy (people present?) → acceptable residue and clean-up → enclosure integrity → environmental limits (ODP/GWP) → cost per m³ and refill availability.
- Agent limits to remember: foam is useless on pressurised gas and Class D; CO₂ at design concentration is lethal; dry powder ruins electronics and loses to re-ignition from hot surfaces; water is forbidden on Class D and on deep fat fryers.
Foam systems
- Foam is an aggregate of air-filled bubbles made from a foam concentrate, water and air. It extinguishes by blanketing the surface (excluding air), cooling with its water content, suppressing vapour release and separating flame from fuel.
- Expansion ratio = volume of finished foam / volume of foam solution: low expansion up to 20:1 (tank and spill fires, monitors, sprinklers), medium 20–200:1, high 200:1 to about 1,000:1 (basements, cable tunnels, hangars, warehouse flooding).
- Concentrate types:
- Protein and fluoroprotein (FP) — good burnback and heat resistance, used for subsurface injection.
- AFFF (aqueous film-forming foam) — spreads an aqueous film ahead of the blanket, fastest knockdown, works through non-aspirating sprinklers.
- FFFP (film-forming fluoroprotein) — AFFF speed with protein heat resistance.
- AR-AFFF / alcohol-resistant — a polymer membrane resists polar solvents (ethanol, methanol, acetone, MTBE blends); sold as 3×3 or 3×6 (3% on hydrocarbons, 6% on polar solvents).
- Fluorine-free (F3) — PFAS-free synthetic foams now replacing AFFF; typically need higher application rates and strictly aspirated discharge devices, and must be requalified on the actual fuel.
- Class A foam — wetting agent at 0.1–1% for solid fuels; high-expansion detergent concentrates for volume flooding.
- Induction rates: 1%, 3% and 6%; the concentrate must match the proportioner and the discharge device — mixing brands or devices invalidates listings.
- Proportioning methods: in-line venturi inductor/eductor (cheap, high pressure loss, fixed flow), around-the-pump proportioner, bladder (pressure-proportioning) tank (no power needed — standard for tank farms and sprinkler-foam), balanced-pressure pump proportioner (wide flow range, accurate), positive-displacement/variable-orifice and batch mixing in a tender.
- Discharge devices: air-aspirating foam branch pipes and nozzles, foam chambers / Type II pourers on fixed-roof tanks, high-back-pressure foam makers for subsurface injection, rim-seal pourers for floating roofs, foam-water sprinklers and spray nozzles (NFPA 16 type), HVLR foam monitors (fixed and trailer-mounted), and high-expansion generators (blower or water-motor driven).
- Tank protection schemes: fixed-roof tanks — top pourers or subsurface injection; subsurface cannot be used for polar solvents or for floating-roof tanks; external floating roof — seal-area protection at a much higher rate over the annular seal area only; internal floating roof — treated as fixed roof with modifications. Bund/dyke areas get monitors and hose streams.
- Foam quality tests: expansion ratio, 25% drainage time (time for a quarter of the solution to drain from the foam — measures stability), seal and burnback resistance; periodic sampling of stored concentrate for sediment, pH and viscosity.
- Indian codes and practice: IS 4989 (foam concentrate for producing mechanical foam, in parts), equipment standards for foam branch pipes and generators, OISD-STD-116 (fire protection in refineries) and OISD-STD-117 (petroleum depots and terminals) prescribe application rates, durations and concentrate stock for the hydrocarbon sector, generally more conservative than NFPA 11 minima; PESO licenses tank installations under the Petroleum Rules, 2002.
- Environmental note: PFOS and PFOA are listed under the Stockholm Convention, to which India is a party, so legacy AFFF stocks and firewater containment are now a compliance issue; the global direction of travel is fluorine-free foam, and any changeover needs full system flushing and re-rating.
Carbon dioxide systems
- Colourless, odourless, non-conducting, leaves no residue; stored as a liquid under its own vapour pressure (about 58 bar at 21 °C in high-pressure cylinders, or refrigerated low-pressure bulk at about 20 bar, −18 °C).
- Acts mainly by oxygen dilution, with some cooling from the expanding gas and dry-ice snow.
- Total flooding: minimum design concentration 34% for surface fires of most hydrocarbons (higher by a material conversion factor for agents like acetylene, hydrogen, ethylene oxide); deep-seated fires in paper, cable insulation or dust need 50–75% with an extended holding time of 20 minutes or more.
- Discharge time: surface fires 1 minute; deep-seated fires, the design quantity within 7 minutes with 30% reached in the first 2 minutes.
- Local application: nozzles aimed at the hazard (quench tanks, printing presses, dip tanks), rate-by-area or rate-by-volume method, minimum 30 seconds discharge.
- Life safety is the dominant issue — 34% CO₂ is lethal, 5% is already dangerous. Mandatory features: pre-discharge alarm and time delay (typically 30 s), manual lock-off/abort, discharge warning signs, odourisers where used, self-closing doors, and strict evacuation drills. Fatalities in CO₂ systems are nearly always maintenance staff inside a flooded space.
- Cylinders are pressure vessels under PESO's gas cylinder rules; fill ratio about 0.667 kg/L (a 68-litre cylinder holds 45 kg). Design per IS 6382 (code of practice for fixed CO₂ systems) and NFPA 12.
- Still the default for marine machinery spaces, ship holds, turbine and generator enclosures, coal mills, and large electrical equipment — because it is cheap, has zero ODP and GWP 1, and is unaffected by the Kigali Amendment.
Halons, the phase-out, and clean agents
- Halon 1301 (CF₃Br, total flooding at about 5%) and Halon 1211 (CF₂ClBr, portables and local application) were ideal agents — low concentration, low toxicity, no residue — but ODP of roughly 10 and 3. Production and consumption were phased out under the Montreal Protocol (developing countries including India by 1 January 2010); only recovered banked halon for essential uses such as civil aviation and some defence applications remains. Installing a new halon system is not permissible.
- A clean agent (NFPA 2001 / ISO 14520 definition) is electrically non-conducting, volatile or gaseous, and leaves no residue on evaporation. Two families:
- Halocarbons — chemical chain-breaking plus heat absorption: HFC-227ea (FM-200), HFC-125 (FE-25), HFC-23 (FE-13), HCFC Blend A (NAF S-III) and the fluoroketone FK-5-1-12 (Novec 1230 type). Low design concentrations (4–12%), 10-second discharge, small cylinder footprint.
- Inert gases — pure oxygen dilution: IG-01 (argon), IG-100 (nitrogen), IG-55 (50/50 N₂/Ar, Argonite), IG-541 (52% N₂, 40% Ar, 8% CO₂, Inergen). Design 34–50%, stored at 200–300 bar, discharge in 60 seconds, zero ODP and zero GWP, no decomposition products.
- Toxicology limits: the design concentration in a normally occupied space must stay below the NOAEL (no observed adverse effect level); between NOAEL and LOAEL only with time-limited egress justification. HFC-227ea: NOAEL 9%, LOAEL 10.5% — so a 7% Class A design is acceptable but a high Class B design may not be. Inert gases are limited by residual oxygen: design concentrations above roughly 43% (O₂ below about 12%) need egress-time justification.
- Decomposition: halocarbons passing through flame produce hydrogen fluoride (HF); HF production rises sharply with longer pre-burn time, which is why early detection and 10-second discharge matter. Inert gases produce nothing.
- Environmental ranking: FK-5-1-12 GWP about 1 with a 5-day atmospheric life; inert gases GWP 0; HFC-227ea GWP in the 3,000+ range (AR4 basis) and therefore inside the Kigali Amendment HFC phase-down, which India has ratified — India's schedule begins with a freeze in 2028 and steps down to an 85% reduction by 2047, so HFC agents will get costlier and harder to refill over the life of a system installed today. Commercial supply of some fluorinated agents is also shifting as manufacturers exit PFAS chemistry; confirm current availability before specifying.
- Enclosure requirements — the most common design failure: the agent must be held at concentration for a specified retention/hold time (commonly 10 minutes), verified by a door-fan integrity test rather than a discharge test. This needs sealed cable entries, dampered HVAC, and pressure-relief venting — critical for inert gases, which add roughly 40–50% to the enclosure volume.
- Indian practice: IS 15493 (gaseous fire extinguishing systems — code of practice), NBC 2016 Part 4 for where fixed suppression is required, and NFPA 2001 / ISO 14520 for agent-specific calculation. Cross-zoned smoke detection, abort and manual release stations, and interlocked HVAC shutdown are standard.
Water mist, dry chemical, wet chemical and aerosol
- Water mist (NFPA 750): droplet spectrum with Dv0.99 under 1,000 µm; extinguishes by evaporative cooling, local oxygen displacement by steam and radiation attenuation. Classified low pressure (under 12.1 bar), intermediate (12.1–34.5 bar) and high pressure (above 34.5 bar). Uses 1/10th the water of sprinklers — favoured for machinery spaces, turbine lube-oil skids, heritage buildings, metro rolling stock and as a halon substitute on ships. Systems are listed only for specific tested applications; do not extrapolate a listing.
- Dry chemical powder (DCP): sodium bicarbonate (BC), potassium bicarbonate (Purple-K, about twice as effective as sodium bicarbonate on Class B), potassium chloride, monoammonium phosphate (ABC/multipurpose — melts to a crust, good on Class A but mildly corrosive and conducting when damp). Acts by radical scavenging; extremely fast knockdown, no cooling, so hot-surface re-ignition is the risk. Used in LPG bottling plants, loading gantries, cable-car and vehicle systems, wheeled 25–75 kg units and fixed skids.
- Class D agents: graphite-based, ternary eutectic chloride (TEC), sodium chloride (Met-L-X) for magnesium, sodium, potassium, lithium, titanium and zirconium. Never water, foam, CO₂ or ABC powder on burning reactive metals.
- Wet chemical (Class K/F): potassium acetate, carbonate or citrate solution for commercial kitchens; it saponifies hot cooking oil into a soapy crust that seals the surface while cooling it. Modern vegetable oils and high-efficiency fryers made dry powder inadequate — hence the UL 300 test regime and NFPA 17A hood/duct/plenum/fryer nozzle layout, with automatic fuel and power shut-off on actuation.
- Condensed aerosol (NFPA 2010): a solid potassium-salt generator combusts to release sub-micron particulate that scavenges radicals; no pressure vessel, no piping, design density in g/m³. Suited to small unoccupied enclosures — switchgear cubicles, EV battery and engine compartments, telecom shelters; residue is fine and hygroscopic, and the generator is hot during discharge.
Design, commissioning and maintenance workflow
- Hazard analysis — fuel, quantity, geometry, enclosure volume and leakage, occupancy, ignition sources, insurance and statutory requirements.
- Agent and strategy selection — total flooding vs local application vs foam blanket; compare life-cycle cost including refill.
- Quantity calculation at the worst-case (lowest expected) temperature and site altitude, with the correct safety and material-conversion factors.
- Hydraulic calculation — two-phase flow for halocarbons, manufacturer-listed software only; nozzle selection, pipe schedule, orifice plates.
- Detection and control — cross-zoned detection, time delay, abort, HVAC and damper interlocks, mechanical manual release, monitored releasing circuits.
- Commissioning — door-fan enclosure integrity test, puff/blow test of pipework, functional cause-and-effect test, foam concentrate induction check and foam quality sampling.
- Maintenance — cylinder weight or pressure check (halocarbons by weight, typically twice yearly; inert gases by pressure), hydrostatic retest intervals for cylinders, foam concentrate condition testing, annual integrity retest, hose and monitor exercising. Occupational safety duties for these systems now sit under the OSH&WC Code, 2020 (in force 21 November 2025), which replaced the Factories Act.
Key points
- Expansion ratio — finished foam volume ÷ solution volume; low ≤20:1, medium 20–200:1, high up to about 1,000:1.
- 25% drainage time — time for a quarter of the water to drain out of the foam; the standard measure of blanket stability.
- AR-AFFF — only foam family valid on polar solvents; plain AFFF is destroyed by alcohol.
- Subsurface injection — foam pushed in below the liquid through high-back-pressure makers; not for polar solvents or floating-roof tanks.
- Rim-seal protection — external floating roofs are protected over the annular seal area at a high rate for a short duration, not over the whole tank area.
- Bladder tank — pressure-proportioning foam unit needing no power; the workhorse of Indian tank farms and foam-sprinkler systems.
- CO₂ minimum design concentration — 34% for surface fires; 50–75% plus extended hold for deep-seated fires.
- CO₂ is an asphyxiant at design concentration — pre-discharge alarm, 30-second delay and lock-off are mandatory, not optional.
- Clean agent — non-conducting, volatile, residue-free; halocarbon or inert gas.
- Cup-burner test — laboratory measurement of extinguishing concentration; design concentration = extinguishing × safety factor (1.2 Class A, 1.3 Class B minimum per NFPA 2001).
- NOAEL/LOAEL — toxicity ceilings that cap the design concentration permitted in occupied spaces.
- Discharge times — halocarbons 10 s, inert gases 60 s, CO₂ 1 min (surface) / 7 min (deep-seated).
- Hold time — 10 minutes typical retention, proved by a door-fan integrity test, not by discharging agent.
- Pressure venting — inert gas discharge raises enclosure volume 40–50%; without relief vents, walls and doors fail.
- HF formation — halocarbons decompose in flame to hydrogen fluoride; fast detection limits it.
- Halon 1301/1211 — phased out under the Montreal Protocol (India by 2010); only banked halon for essential uses.
- Kigali Amendment — HFC agents (FM-200, FE-25) face a phase-down India begins in 2028; FK-5-1-12 and inert gases are not affected.
- Wet chemical saponifies cooking oil; dry powder does not and is no longer acceptable for modern fryers.
Formulas and examples
Concentrate volume: Vc = Q × (P/100) × t — P = induction percentage (1, 3 or 6), t = design duration (min)
Water required = Q × (1 − P/100) × t, plus supplementary hose streams and the firewater reserve
Expansion ratio E = volume of finished foam ÷ volume of foam solution used
CO₂ total flooding: W = (V × F × Kb) + wall/opening allowance — V = enclosure volume (m³), F = flooding factor (kg/m³, from the code table), Kb = material conversion factor
Halocarbon clean agent: W = (V / s) × [C / (100 − C)] — W = agent mass (kg), s = agent vapour specific volume (m³/kg), C = design concentration (% v/v)
s = k₁ + k₂ × T (HFC-227ea: s ≈ 0.1269 + 0.000513 T; FK-5-1-12: s ≈ 0.0664 + 0.000274 T, T in °C)
Inert gas: X = 2.303 × (Vs/S) × log₁₀[100 / (100 − C)] — X = m³ of agent (at NTP) per m³ of enclosure
Residual oxygen after inerting: O₂ (%) = 20.9 × (100 − C) / 100
Design concentration = cup-burner extinguishing concentration × safety factor (≥1.2 Class A, ≥1.3 Class B)
Example 1 — foam for a fixed-roof crude tank (top pourers). Tank diameter 30 m, 3% AFFF, application rate 4.1 L/min·m², duration 55 min (low flash point), plus three supplementary hose streams of 189 L/min for 30 min.
- Area A = (π/4) × 30² = 706.9 m².
- Solution rate Q = 706.9 × 4.1 = 2,898 L/min.
- Concentrate for pourers = 2,898 × 0.03 × 55 = 4,782 L.
- Hose streams: 3 × 189 = 567 L/min → concentrate = 567 × 0.03 × 30 = 510 L.
- Total concentrate = 4,782 + 510 ≈ 5,292 L → specify a 6,000 L bladder/storage tank.
- Water = (2,898 + 567) × 0.97 × 55 ≈ 184,900 L for the main period; size the firewater reserve to the governing scenario, not just this tank.
(Rate and duration here follow NFPA 11 minima; for an OISD-covered refinery or terminal, use the OISD-specified rate and duration, which are usually higher.)
Example 2 — CO₂ total flooding of a switchgear room. Room 10 × 6 × 3 m, surface fire, 34% design, flooding factor 0.80 kg/m³ for this volume band, Kb = 1.0, no unclosable openings.
- V = 180 m³ → W = 180 × 0.80 × 1.0 = 144 kg.
- Using 68-litre cylinders filled at 0.667 kg/L = 45 kg each: 144 / 45 = 3.2 → 4 cylinders (180 kg installed).
- Discharge in 1 minute; add a 30-second pre-discharge delay, abort station and signage. If the space is manned, re-examine the choice of agent — 34% CO₂ is lethal.
Example 3 — HFC-227ea (FM-200) for a server room. Room 8 × 5 × 2.8 m, design concentration 7% (Class A), minimum expected temperature 20 °C.
- V = 112 m³; s = 0.1269 + 0.000513 × 20 = 0.13716 m³/kg.
- W = (112 / 0.13716) × (7 / 93) = 816.6 × 0.07527 = 61.5 kg → select 62 kg plus the uncloseable-opening allowance.
- Check 7% < NOAEL 9% → acceptable for an occupied space. Discharge in 10 s; prove a 10-minute hold by door-fan test.
Example 4 — IG-541 (Inergen) for the same room. Design 37.5% at 20 °C, so Vs/S ≈ 1.
- X = 2.303 × 1 × log₁₀(100 / 62.5) = 2.303 × 0.2041 = 0.470 m³ of agent per m³ of room.
- Agent volume = 112 × 0.470 = 52.6 m³ at atmospheric conditions.
- 80-litre cylinders at 200 bar give roughly 15 m³ of free gas each → 52.6 / 15 ≈ 3.5 → 4 cylinders.
- Residual oxygen = 20.9 × 0.625 = 13.1% — survivable for short egress, but the room needs a relief vent for the ~47% volume increase, and a cylinder bank far bigger than the FM-200 equivalent.
| Agent | Family | Typical design conc. | Discharge time | ODP | GWP | Main strength / limit |
|---|---|---|---|---|---|---|
| CO₂ | Inert | 34% (surface) | 1 min | 0 | 1 | Cheap, no phase-down; lethal, high-pressure hazard |
| HFC-227ea | Halocarbon | 7% (A), 9% (B) | 10 s | 0 | ~3,200 | Compact storage; Kigali phase-down, HF on decomposition |
| HFC-125 | Halocarbon | ~8–11% | 10 s | 0 | ~3,500 | Lower cost per kg; narrow NOAEL margin |
| FK-5-1-12 | Fluoroketone | 4.2–5.9% | 10 s | 0 | ~1 | Large safety margin, 5-day life; costly, supply shifting |
| IG-541 | Inert blend | 37.5% | 60 s | 0 | 0 | No decomposition; many high-pressure cylinders, venting needed |
| IG-55 / IG-100 | Inert | 37–47% | 60 s | 0 | 0 | Cheap refill from industrial gas; large cylinder bank |
| Water mist | Water | By listing | Continuous | 0 | 0 | Minimal water damage; listing-specific only |
| AFFF / F3 foam | Foam | 1/3/6% at 4.1+ L/min·m² | Continuous | — | — | Only answer for pool fires; PFAS issue with AFFF |
Where it is used
- Refineries, terminals and tank farms (IOCL, BPCL, HPCL, Reliance, Nayara, ONGC): fixed foam pourers, subsurface injection, rim-seal systems, HVLR monitors, foam tenders, designed to OISD-STD-116/117 and licensed under PESO.
- Data centres, UPS and server rooms, telecom exchanges, control rooms: FK-5-1-12 or inert-gas clean-agent systems with cross-zoned detection — the biggest growth area in Indian fire-system sales.
- Power plants and industry: CO₂ for turbo-generator and coal-mill enclosures, cable galleries and transformer rooms; high-expansion foam in cable tunnels; water mist on lube-oil skids and in metro rolling stock.
- Ships and offshore platforms: CO₂ for machinery spaces and cargo holds, foam on deck and helidecks, water mist as a halon replacement, inspected under SOLAS/FSS by recognised organisations and the Directorate General of Maritime Administration.
- Aviation, kitchens and vehicles: airport crash tenders with foam monitors and DCP, hangar high-expansion and foam-water systems, wet chemical hood systems in hotel and QSR kitchens, DCP and aerosol systems in buses and EV battery enclosures.
- Job roles: fire protection design engineer, EPC proposal engineer, commissioning and AMC engineer, safety officer in a hazardous-process factory, insurance risk surveyor, third-party inspector, and fire-equipment manufacturing and testing roles.
Interview questions
- Q: Why is foam not used on pressurised gas fires? A: Foam works by blanketing a liquid surface; a pressurised gas jet has no pool to cover and the leak must be isolated — otherwise you create an unignited gas cloud, which is more dangerous.
- Q: What makes AFFF different from protein foam? A: AFFF releases a thin aqueous film from the fluorosurfactant that spreads ahead of the blanket for very fast knockdown and works through non-aspirating nozzles; protein foam is slower but more heat- and burnback-resistant.
- Q: Why can't ordinary AFFF be used on an ethanol fire? A: Alcohol is miscible with water and draws the water out of the bubbles, collapsing the blanket; an alcohol-resistant (AR-AFFF) concentrate forms a polymer membrane between fuel and foam.
- Q: Where is subsurface foam injection not permitted? A: On floating-roof tanks and on polar-solvent service, and where the foam would be degraded by travelling through the fuel.
- Q: Why is a CO₂ system risky even when designed correctly? A: The 34% design concentration is immediately life-threatening; most CO₂ deaths involve staff inside or entering the protected space, so pre-discharge alarms, time delay, lock-off and procedural control matter as much as the hydraulics.
- Q: Difference between total flooding and local application? A: Total flooding fills a whole enclosure to a design concentration and relies on enclosure integrity; local application discharges directly onto an unenclosed hazard surface for a set time.
- Q: Why do halocarbons discharge in 10 seconds and inert gases in 60? A: Halocarbons must reach concentration before significant thermal decomposition to HF occurs; inert gases produce no decomposition products and are discharged slower to limit over-pressure and turbulence.
- Q: What is the door-fan test and why not just discharge the agent? A: It pressurises the room with a calibrated fan to measure total leakage area and predict the retention time; a discharge test is costly, polluting and proves only that one day's conditions were sealed.
- Q: Why is FK-5-1-12 preferred over FM-200 in new designs? A: It has a GWP of about 1 and a 5-day atmospheric life, so it sits outside the HFC phase-down, and its NOAEL gives a wide safety margin over the design concentration.
- Q: What replaced halon 1301 and why was it banned? A: It had an ozone depletion potential of about 10 and was phased out under the Montreal Protocol; replacements are halocarbon clean agents, inert gases, water mist and CO₂ — none matching halon on all counts.
- Q: Why is a wet chemical agent, not DCP, used over a deep fat fryer? A: It saponifies the hot oil into a sealing soap layer while cooling it; powder knocks the flame down but leaves the oil above its auto-ignition temperature, so it re-ignites.
- Q: An inert-gas system is installed in a sealed room with no vent. What happens on discharge? A: The agent adds roughly 40–50% to the enclosure volume, and the resulting over-pressure can blow out doors, ceilings or walls — pressure-relief venting is a design requirement.
Common mistakes
- Calculating foam concentrate from the tank area only and forgetting supplementary hose streams, the pump/bund protection and the stated duration.
- Confusing foam solution flow with concentrate flow, or applying the 3% figure to the wrong one.
- Using the whole tank area for an external floating roof instead of the annular seal area, and the seal rate instead of the full-surface rate for a fixed-roof tank.
- Treating CO₂ as a clean agent for occupied spaces — it is a clean agent chemically but an asphyxiant at design concentration.
- Taking the cup-burner extinguishing concentration as the design concentration, omitting the 1.2/1.3 safety factor, or computing agent mass at room temperature when a lower minimum temperature governs.
- Designing a clean-agent system without an enclosure integrity test, pressure-relief venting or HVAC/damper interlock — the agent then leaks away long before the 10-minute hold.
- Specifying a foam concentrate, proportioner and discharge device from different listings, or assuming a fluorine-free foam drops into an AFFF system at the same application rate.
Related topics