Knowledge / Electrical and Electronics Engineering / Excitation systems and generator protection

Excitation systems and generator protection

Electrical and Electronics Engineering (B.E./B.Tech) · Electrical machines · free study notes for exams, placements and interviews

In short

An excitation system supplies and controls the DC current in a synchronous generator's field winding, and so fixes its internal EMF — which in turn fixes terminal voltage, reactive power output and transient stability margin. Generator protection is the set of relays that detects stator, rotor, excitation and prime-mover faults and abnormal operating conditions, and trips the machine before damage occurs. Together they are the "control and safety" half of power-plant electrical engineering, examined in electrical machines and power-system protection papers and in GATE (EE), and assessed in interviews at NTPC, NHPC, NLC, SJVN, Power Grid, state gencos, BHEL, L&T, Siemens Energy, GE Vernova, ABB/Hitachi Energy, Tata Power and Adani Power. In India the requirements are mandatory, not optional: the Indian Electricity Grid Code and CEA regulations require AVR in continuous service, specified reactive capability and specified protection on every grid-connected unit.

Explained

Why excitation is needed and what limits it

Types of excitation system

  1. DC (rotating) excitation — conventional. A shaft-mounted DC shunt/separately-excited main exciter, often with a smaller pilot exciter, feeds the field through slip rings and brushes. Simple and robust, but slow (exciter time constant 0.3–1 s), with commutator and brush maintenance. Modelled as IEEE Type DC1A/DC2A.
  2. Static (bus-fed / potential-source) excitation. A step-down excitation transformer from the generator terminals (or auxiliary bus) feeds a thyristor (SCR) full-wave bridge, whose DC output goes to the field through slip rings. Response is almost instantaneous (≈ 20–50 ms), ceiling voltage high, and it allows negative field forcing and fast de-excitation. Drawback: at a close-in fault the terminal voltage collapses, so the source collapses too — hence compound-source (current + potential) schemes, and field flashing needed at start-up. Model: IEEE Type ST1A.
  3. Brushless (rotating-rectifier) excitation. A shaft-mounted AC exciter (inverted alternator) feeds a rotating diode bridge on the shaft, which feeds the field directly — no slip rings, no brushes. A permanent-magnet generator (PMG) pilot exciter makes it self-contained and fault-independent. Used widely in DG sets and aero/marine sets; slower than static, no direct access for rotor earth-fault measurement or forced de-excitation. Model: IEEE Type AC5A/AC8B.
  4. Static excitation with digital AVRs (dual-channel, hot-standby) is standard in new Indian thermal units; excitation system standards are IEC 60034-16 series and IEEE 421.1/421.2/421.4/421.5 (models and specification).

AVR loop, limiters and the power system stabiliser

Field flashing, de-excitation and field forcing

Generator neutral earthing and fault behaviour

Generator protection functions (ANSI/IEEE device numbers)

DeviceFunctionWhat it protects against
87G / 87T / 87GTBiased differential (generator, transformer, overall unit)Stator and GT phase faults
87N / 64REFRestricted earth fault (high impedance)Winding earth faults near the neutral
64G, 59N, 27TN/59THStator earth fault — neutral overvoltage, third-harmonic, 20 Hz low-frequency injection for 100% stator earth-fault coverEarth faults including the neutral end and at standstill
64F / 64RField (rotor) earth fault, DC injection or AC injectionRotor winding insulation failure
40Loss of field / loss of excitation (two offset mho zones)Field failure, AVR/exciter failure, open field
46Negative-sequence (I₂²t) overcurrentRotor surface heating from unbalanced load, open phase, unbalanced fault
51VVoltage-restrained / voltage-controlled overcurrentBackup for system faults (plain 51 cannot work: fault current decays below rated)
21Distance (backup)Uncleared transmission faults
32R / 32LReverse power / low forward powerLoss of prime mover (motoring), sequential tripping
24Over-fluxing (V/Hz), definite + inverse timeCore saturation at over-voltage or low frequency, especially on run-up
27 / 59Under / over-voltageInsulation stress, AVR failure
81U / 81O / 81RUnder / over-frequency, df/dtTurbine blade fatigue, islanding
78Out-of-step / pole slipping (impedance locus)Loss of synchronism — must trip at a safe pole-slip angle
49 / RTDThermal overload, stator and bearing temperatureOverheating, cooling failure
50/27Inadvertent energisation ("dead machine")Closing the breaker on a standstill machine
60VT supply supervision (fuse failure)Blocks 40, 21, 51V, 32 on false voltage
12 / 14 / 37Over-speed, under-speed, undercurrentMechanical over-speed, loss of load
86 / 94Lockout and master trip relaysRoutes trips to breaker, field breaker, turbine, CO₂/boiler

Key points

Formulas and examples

E_f = V + I_a (R_a + jX_s) — internal EMF per phase; V terminal voltage (V), I_a armature current (A), X_s synchronous reactance (Ω or pu)
I_f ≈ (E_f / E_rated) × I_f0 — field current estimate on the air-gap line; I_f0 = no-load field current for rated voltage (A)
Q = (E_f V cos δ − V²) / X_s ; P = E_f V sin δ / X_s — per phase, SI units W/VAR
Z_base = V_LL² / S_base (Ω); Z_secondary = Z_primary × (CT ratio / VT ratio)
Response ratio = [∫₀0.5 (v_f − V_fr) dt] / (V_fr × 0.5) — per unit field volts per second
Field energy W = ½ L_f I_f² (J); discharge time constant τ = L_f / (R_f + R_d) (s); peak induced volts = I_f R_d
I₂² t = K — negative-sequence short-time withstand; I₂ in pu of rated stator current, t in s, K in s (typ. 30 indirectly cooled cylindrical rotor, 40 salient pole with amortisseur, 10 or less for directly cooled — follow the machine's data sheet)
V/Hz = (V/V_rated) / (f/f_rated) — per unit over-fluxing measure
Earth-fault current with distribution-transformer earthing: I_f = V_phase / (n² R_sec), n = primary/secondary turns ratio
Relay 40 mho: Zone 1 diameter = 1.0 pu, Zone 2 diameter = X_d, offset = −X′_d / 2 (pu)

Example 1 — excitation needed at rated load. 50 MVA, 11 kV, 3-phase star generator, X_s = 1.2 pu, R_a negligible, operating at rated MVA and 0.85 pf lagging. No-load field current for rated voltage on the air-gap line = 500 A.

Example 2 — sizing the neutral earthing resistor. 11 kV generator, high-resistance earthed through an 11,000/240 V distribution transformer; earth-fault current to be limited to 10 A.

Example 3 — negative-sequence (46) withstand. 250 MVA, 15.75 kV directly-cooled turbo-generator, continuous I₂ capability 8%, K = 10 s. An open phase on the HV side produces I₂ = 0.35 pu.

Example 4 — loss-of-field (40) relay settings in secondary ohms. 200 MVA, 13.8 kV machine, X_d = 1.8 pu, X′_d = 0.25 pu, CT 10,000/5, VT 13,800/110.

Example 5 — de-excitation. Field inductance L_f = 2.2 H, field resistance R_f = 0.35 Ω, field current 1,200 A; peak rotor insulation stress to be kept below 2 kV.

Excitation typeResponseBrushesField forcing / de-excitationTypical use
DC rotating exciterSlow (0.3–1 s)YesLimited, ceiling ~1.6–2 puOlder thermal and hydro sets
Static (thyristor, bus-fed)Very fast (20–50 ms)Yes (slip rings)Excellent, incl. negative forcingModern large units, most 660/800 MW sets (many BHEL 500 MW sets are brushless)
Brushless (rotating diodes + PMG)ModerateNoPoor (no access to field circuit)DG sets, marine, aero, small hydro

Where it is used

Interview questions

Common mistakes

Related topics

Synchronous machines · Power system protection and switchgear · Power system stability and load-frequency control · Transformers (generator-transformer protection) · Switchgear, circuit breakers and relay testing · Power system operation and the Indian grid code.