Knowledge / Electrical and Electronics Engineering / Synchronous machines

Synchronous machines

Electrical and Electronics Engineering (B.E./B.Tech) · Electrical machines · free study notes for exams, placements and interviews

In short

A synchronous machine is an AC machine whose rotor runs in exact step with the rotating field of the stator, at the synchronous speed Ns = 120f/P. As a generator (alternator) it produces most of India's electricity - every thermal, hydro and nuclear set at NTPC, NHPC, NPCIL, Tata Power and the captive stations is a synchronous generator; as a motor it drives large constant-speed compressors and mills and corrects power factor as a synchronous condenser. It is the heaviest-weighted topic in electrical machines for GATE, ESE, state PSU and PSU recruitment (NTPC, PGCIL, BHEL, SAIL, DVC, state electricity boards), and the base for all power-system stability study. Examination focuses on voltage regulation methods, the power-angle relation, parallel operation and the salient-pole two-reaction theory.

Explained

Construction, types and ratings

EMF equation, winding factors and the air-gap field

Armature reaction and the equivalent circuit

Voltage regulation and its determination

Two-reaction (Blondel) theory for salient-pole machines

Power-angle relation, operating limits and the synchronous motor

Parallel operation and synchronisation

Key points

Formulas and examples

Ns = 120 f / P rpm; f = P Ns / 120 Hz (f in Hz, P = number of poles, Ns in rpm)
E_ph = 4.44 Kc Kd f φ T volts (φ = flux per pole in Wb, T = turns per phase, Kc = pitch factor, Kd = distribution factor)
Kc = cos(α/2); Kd = sin(mβ/2) / [m sin(β/2)] (α = short-pitch angle, m = slots/pole/phase, β = slot angle in electrical degrees)
E = V + I (Ra + j Xs) generator; E = V − I (Ra + j Xs) motor (all per phase, volts, ohms, amperes)
|E| = √[(V cosφ + I Ra)² + (V sinφ ± I Xs)²] (+ lagging, − leading pf)
% Regulation = (E − V) / V × 100
Zs = Voc(line-to-neutral) / Isc at the same field current; Xs = √(Zs² − Ra²)
SCR = If for rated Voc / If for rated Isc ≈ 1 / Xd(pu)
Salient pole: tan(δ + φ) = (V sinφ + I Xq)/(V cosφ + I Ra); E = V cosδ + Id Xd (Ra neglected)
P (cylindrical) = 3 E V sinδ / Xs watts; Pmax at δ = 90°
P (salient) = 3[ E V sinδ / Xd + V²(Xd − Xq) sin2δ / (2 Xd Xq) ]
Q = 3 V (E cosδ − V) / Xs vars; Synchronising power Psy = (3 E V / Xs) cosδ per electrical radian
Slip test: Xd = Vmax / Imin, Xq = Vmin / Imax
Tsh = 9.55 × Pout(W) / Ns(rpm) N·m; motor input per phase P = V I cosφ

Example 1 - Speed, poles and EMF constants. A 50 Hz, 3-phase alternator is directly coupled to a hydro turbine running at 375 rpm. Its stator has 180 slots, the winding is short-pitched by one slot.

Example 2 - Regulation by the EMF method. A 3-phase, star-connected, 11 kV, 10 MVA alternator has Ra = 0.4 Ω/phase and Xs = 6 Ω/phase. Find the regulation at full load, 0.8 pf lagging and 0.8 pf leading.

Example 3 - Power angle, synchronising power and pull-out. The same machine (Xs = 6 Ω, Ra neglected) delivers 6 MW to an 11 kV infinite bus with E = 8,744 V/phase.

Example 4 - Salient-pole machine, two-reaction theory. A 3-phase star-connected salient-pole alternator, 1 kV line, Xd = 4 Ω, Xq = 2 Ω per phase, Ra ≈ 0, delivers 100 A at 0.8 pf lagging. Find δ, E and the regulation.

Example 5 - Synchronous condenser for power-factor correction. A plant draws 1,200 kW at 0.7 pf lagging. A synchronous motor is added that itself takes 200 kW (assume unity-pf mechanical load inside it) and the combined pf must be 0.9 lagging. Find the leading kVAR the motor must supply.

FeatureCylindrical (turbo) rotorSalient-pole rotor
Poles / speed2-4 poles, 1500-3000 rpm6-80 poles, 75-1000 rpm
ShapeSmall diameter, long axial lengthLarge diameter, short length
Prime moverSteam, gas turbineHydro turbine, diesel engine
Air gapUniform, Xd ≈ XqNon-uniform, Xd > Xq
AnalysisSingle synchronous reactanceTwo-reaction (Blondel) theory
Windage / noiseLow (smooth rotor)Higher
Damper windingRotor body gives damping actionExplicit damper bars in pole faces
MethodCurves neededSaturation handledResult
EMF (synchronous impedance)OCC + SCCNo (air line)Pessimistic - too high
MMF (ampere-turn)OCC + SCCPartly (saturated OCC)Optimistic - too low
ASAOCC + SCC + correctionYesClose to actual
Potier (ZPF)OCC + ZPF curve + SCCYes (separates XL)Most accurate
QuantitySynchronous motorThree-phase induction motor
Speed with loadConstant at NsFalls with slip
Power factorAdjustable, can be leadingAlways lagging
StartingNot self-startingSelf-starting
ExcitationSeparate DC field neededNone (induced)
Typical useLarge compressors, mills, pf correctionGeneral drives

Where it is used

Interview questions

Common mistakes

Related topics

Transformers · DC machines · Induction motors · Excitation systems and generator protection · Special machines: stepper and BLDC motors · Electrical machine design basics

Open in the Knowledge reader →Find jobs →