Knowledge / Electrical and Electronics Engineering / Underground cables

Underground cables

Electrical and Electronics Engineering (B.E./B.Tech) · Power systems · free study notes for exams, placements and interviews

In short

An underground cable carries power through a conductor surrounded by solid insulation, a metallic earthed sheath and mechanical protection, buried in the ground instead of strung in air. It is the standard choice for urban distribution, industrial plants, substation interconnections, river and runway crossings, and increasingly for EHV links in Indian metros. Because the insulation is thin and the field is radial and intense, the examinable theory is almost entirely about electric stress, grading, capacitance, dielectric loss, heating and fault location. It is a scoring GATE/university topic and a routine interview area for roles in state DISCOMs, Power Grid, Tata Power, Adani, L&T, Sterlite, Polycab, KEI, Havells, RR Kabel and EPC contractors working under RDSS urban underground-cabling packages.

Explained

Construction and materials

Classification

Electric stress and grading

Capacitance, charging current and dielectric loss

Heating, current rating and losses

Laying, accessories, testing and fault location

Underground versus overhead, standards and Indian practice

Key points

Formulas and examples

Insulation resistance: R_ins = (ρ / 2πl) · ln(R/r) — ρ = resistivity of insulation (Ω·m), l = length (m), r = conductor radius, R = inner sheath radius (same units). Note the inverse dependence on l.
Capacitance: C = 2πε₀εr / ln(R/r) F/m, i.e. C = 0.02416 εr / log₁₀(R/r) μF/km — εr = relative permittivity.
Electric stress at radius x: g = V / (x · ln(R/r)); gmax = V / (r·ln(R/r)), gmin = V / (R·ln(R/r)); gmax/gmin = R/r. V = voltage between conductor and sheath (use peak value when comparing with dielectric strength in kV/cm peak).
Most economical size: R/r = e = 2.718, r = V / gmax, insulation thickness = r(e − 1) = 1.718 r.
Capacitance grading (3 layers): ε₁r = ε₂r₁ = ε₃r₂; total V = Σ gmax,i · r_(i−1) · ln(r_i/r_(i−1)).
Intersheath grading (one intersheath at r₁ held at V₁ above earth): g₁max = (V − V₁)/(r·ln(r₁/r)), g₂max = V₁/(r₁·ln(R/r₁)); equal stresses give the optimum V₁.
Charging current per phase: Ic = Vph · ω · C; reactive power Qc = Vph² ω C per phase (ω = 2πf).
Dielectric loss per phase: Wd = Vph² · ω · C · tanδ (W), tanδ = loss tangent.
3-core belted cable: CN = Cs + 3Cc (Cs = core–sheath, Cc = core–core).
Thermal: temperature rise Δθ = W × S, W = total watts lost per unit length, S = total thermal resistance (thermal ohms); permissible current I = √(Δθ / (R_ac · S)) ignoring dielectric and sheath loss.
Murray loop: x = 2L · Q / (P + Q) — L = cable length, P and Q the ratio arms, x = distance to fault from the test end (loop of faulty + healthy core of equal resistance per unit length).

Example 1 — Insulation resistance. Single-core cable, conductor diameter 2 cm, inner sheath diameter 5 cm, insulation resistivity 4.5 × 10¹⁴ Ω·cm, length 1 km.

Example 2 — Capacitance, charging current and dielectric loss. Same geometry (r = 1 cm, R = 2.5 cm), εr = 3.5, 33 kV 3-phase 50 Hz, 5 km, tanδ = 0.004.

Example 3 — Stress distribution and economical size. Single-core cable, conductor diameter 3 cm, insulation thickness 1.5 cm, 66 kV between conductor and sheath.

Example 4 — Capacitance of a 3-core belted cable. Bridge tests on an 11 kV, 3-core belted cable: (a) three cores bunched against sheath → 0.9 μF; (b) two cores and sheath bunched against the third core → 0.7 μF. Find CN and the charging current at 50 Hz.

Example 5 — Murray loop fault location. A 2 km cable has an earth fault on one core; the faulty core is looped to a healthy identical core at the far end and the bridge balances with ratio arms P = 70 Ω and Q = 30 Ω (Q adjacent to the faulty core).

FeatureOverhead lineUnderground cable
Capital costLow (reference)Several times higher per km
InsulationAir (self-restoring)Solid, thin, non-self-restoring
Capacitance / chargingLow20–40× higher; needs compensation at EHV
Surge impedance~400 Ω~30–50 Ω
FaultsFrequent, mostly transientRare, almost always permanent
Fault location & repairVisual, hoursInstruments needed, days
Overload capabilityGood (air cooling)Poor (limited heat dissipation into soil)
Public safety, aesthetics, storm immunityPoorExcellent
PropertyImpregnated paperPVCXLPE
Max continuous conductor temp65–85 °C70 °C90 °C
Short-circuit temp~160 °C160 °C250 °C
tanδ0.003–0.01high0.002–0.004
Voltage range in Indialegacy up to 220 kVup to 1.1 kV (11 kV rare)up to 400 kV
JointingSkilled, oil/compoundSimpleHeat-/cold-shrink, pre-moulded

Where it is used

Interview questions

Common mistakes

Related topics

Transmission lines and cables · High-voltage engineering and insulation · Distribution systems and substations · Power system protection: relays and circuit breakers · Power quality and harmonics · HVDC transmission

Open in the Knowledge reader →Find jobs →